Description
The burner control box DKG 972 controls and supervises atmospheric burners for gas. They are approved and certified according to the applicable European standards and regulations. The microprocessor-based programming sequence ensures
extremely stable timings independent of voltage variations,
ambient temperature and/or switch-on cycles.
Specifications:
Specifications:
- Complete reference: DGK972 mod. 05 (0332005), DGK972 mod. 10 (0332010), DGK mod. 10-110vac (0332310) DGK972 mod. 20 (0332020)
- For 2-stage atmospheric gas burners
- Flame detection: Ionisation probe, Infrared-flicker detector IRD 1020, UV flame sensor UVD 971
- Flame detection: Ionisation probe, Infrared-flicker detector IRD 1020, UV flame sensor UVD 971
Model |
Waiting time start tw |
Pre-ignition time tvz |
Stray light monitoring tf |
Safety time ts |
Post-ignition time tn |
Delay 2nd-stage tv2 |
Power supply |
05 (0332005) |
12 |
3 |
5 |
5 |
4.5 |
25 |
220 – 240 V |
10 (0332010) |
10 |
9.5 |
220 – 240 V |
||||
10-110VAC (0332310) |
10 |
9.5 |
110 V |
||||
20 (0332020) |
|
|
|
20 |
19.5 |
|
220 – 240 V |